| Specification:
AC Input 208 VAC or 400 VAC, 3 phase, 50/60 Hz. (Please specify at the time of order).
Average Charging Rate 8000 J/s at rated Output Voltage.
Peak Charging Rate 9000 J/s at rated Output Voltage.
Standard Voltage Ranges 1, 1.5, 2, 3, 4, 5, 6, 10, 15, 20, 30, 40, 50 kV. All models continuously variable from 0 to 100% of rated voltage output. Linear to within 1% of full scale. Accuracy 1% of rated.
Polarity Available as fixed Positive or Negative, Please Specify.
High Voltage Assembly Oil Insulated HV section with optional air insulation at voltages below 6kV
Output Connector/Cable
| Output Voltage |
Connector |
Cable |
| 1-30kV |
Proprietary |
DS 2124 |
| 30-50kV |
Proprietary |
DS 2024SSJ |
| 1-6kV (Air Option) |
Amphenol (HN) |
RG-8/U |
Input Connector
VDE, UL, CSA, approved
Power Factor Passive PFC 0.85 min
Efficiency Better than 85%
Stored Energy Less than 0.3 Joules all models.
| Stability 0.2% per hour after 1 hour warm-up. Pulse to Pulse Repeatability +/- 2% to 1kHz. For higher repetition rates, consult factory
Temperature Coefficient 100 PPM per oC
Ambient Temperature Storage: -40 to +80 oC Operating:0 to +45 oC
Humidity 10-90% Non-condensing
Protection The power supply is protected against open circuits, short circuits, overloads and arcs.
Agency Approvals Certification to EN60950 (pending)
Mechanical 19"(482mm) x 17"(432mm) x 8.75"(222mm) See Datasheet
Accessories - Detachable 10 foot HV cable - Operating manual
Remote Control Via 25pin d-type connector on rear panel.
Click here for Remote Control details.
Options
| Suffix-RFI |
Optional external filter which reduces conducted emissions to meet VDE0871/6.78 Class B. |
| Suffix-5V |
0 to +5 volt program (0 to full-scale output) |
| Suffix-CT |
Optional internal contactor for OEM only (standard on L/S models) | |